Load check and system design

A load check is how we confirm your system size before we install: we go through what you run, what runs at the same time and what must stay on at night. Every order gets one: payment confirms the order, then we contact you to check your load and book the installation.

Want a design before you order, for a large building, three-phase supply or an unusual load? Ask us on WhatsApp.

What a load check covers

  • Every appliance you will run, and its running watts from its label
  • Which ones take a kick when they start: fridges, freezers, pumping machines and washing machines
  • What runs at the same time, and what can wait
  • What must stay on at night, and for how long
  • Heavy items: air conditioners, pressing irons, microwaves and water heaters
  • Where the inverter, battery and panels will go, the space for panels, and any shade
  • Your supply today: public supply, a generator, or neither

Why we check before installation

The calculator is a good start, but it counts one of each item at a typical wattage. Real homes and offices differ: two air conditioners, a bigger pump, a chest freezer as well as a deep freezer. The check makes sure the system carries what you actually run, so it does not trip when everything comes on at once.

If your load needs a different size from the one you ordered, we tell you before we install.

How we work out the size

The rule is simple:

  1. Add the running watts of everything that can be on together.
  2. Find the biggest item that takes a kick at start, and add twice its watts.
  3. Pick the smallest size that carries the total.

Take lights (100 W), fans (225 W), a TV and decoder (150 W), a fridge (150 W) and a freezer (200 W). The freezer has the biggest starting kick, so add twice its 200 W, for 1,225 W in all. That needs 2.5kVA, which carries up to 2,000 W. Add a pumping machine (750 W, with its own kick) and it needs 5kVA, which carries up to 4,000 W.

Battery time follows a second rule: battery kWh × 0.9 × 1000 ÷ the load in watts. A 2.5kVA system running lights, fans and the TV and decoder (475 W) lasts about 9.5 hours on the battery alone. A 5kVA system on the same load lasts about 19 hours.

Panels follow the size: each comes with its own set of 600W panels. The panels guide lists them all.

A design before you order

Some jobs need a design first:

  • large homes and offices with several air conditioners
  • buildings on three-phase supply
  • loads beyond our largest listed size, 20kVA, which carries up to 16,000 W
  • borehole pumps and machines that start hard
  • estates and sites that need street lights

Send us on WhatsApp a list of what you run (photos of appliance labels help), photos of the space for panels and of your distribution board, how long you want backup to last, and your town and state. We come back with the size we suggest and how we would set it up. See also solar for business and offices.

Getting ready for your load check

  • Note the watts on the labels of your main appliances.
  • Decide what must stay on at night, and what can wait for daylight or public supply.
  • Clear a cool, dry spot for the inverter and battery, out of the sun and the rain.
  • Know where the panels can go: a roof or open space with clear sky and little shade.

If you are choosing between inverter types, the hybrid or normal inverter guide explains why every system we install uses a hybrid inverter.

Questions and answers

What size solar system do I need?

Tick what you run in the calculator and it picks the size. We confirm it with a load check before installation.

How many solar panels do I need?

Each size comes with its own set of 600W panels, from 2 at 1.5kVA to 28 at 20kVA. The calculator shows yours.

What happens after I pay?

Payment confirms your order. We then contact you to check your load and book the installation.

Can you design a system for my office or estate before I order?

Yes. Send what you run and your site details on WhatsApp.

What is the load capacity of a 5kVA inverter?

Our 5kVA system carries up to 4,000 W by our sizing rule, which counts running watts plus room for the biggest starting kick. See the 5kVA page for what it runs.

What is a starting kick?

Fridges, freezers, pumping machines and washing machines draw much more for a moment when they start. The calculator adds twice the biggest of those, so the inverter does not trip.

Tell us what you need.